Wartości wtórne:
X1 =14,85 Ω R1ff=7,43 R1fe=15,62
X1w =20,09 Ω R1wff=8,13 R1wfe=16,31
X2 =20,09 Ω R2ff=8,13 R2fe=16,31
X3 =60,00 Ω R3ff=13,45 R3fe=21,64
Measurement: Full Scale Voltage (100%) 220,0 kV
Measurement: Full Scale Current (100%) 1200 A
Line Angle 82 °
Angle of inclination, distance charact. 82 °
Line Reactance per length unit 0,2290 Ohm / km
Line Length 76,3 km
Zero seq. comp. factor RE/RL for Z1 1,60
Zero seq. comp. factor XE/XL for Z1 0,40
Zero seq. comp.factor RE/RL(> Z1) 1,60